The monitoring of insulations that composing high voltage apparatus and electrical machines is a crucial aspect for a predictive maintenance program. The insulation system of an electrical machine is affected by partial discharges (PDs), phenomena that can lead to the breakdown in a certain time, with a consequent and significant economic loss. Partial discharges are identified as both the symptom and the cause of a deterioration of solid-type electrical insulators. Thus, it is necessary to adopt solutions for monitoring the insulation status. To do this, different techniques and devices can be adopted. During this research activity, two different systems have been developed at the circuit and layout level, which base their operation respectively on the conducted and on the irradiated measurement, in compliance with the provisions of current standards, if foreseen. The first system is based on the use of a classic signal conditioning chain in which gain value can be set through PC control, allowing the conducted measurement of partial discharges in two frequency bands, Low Frequency (LF) and High Frequency (HF). Based on these bands, the application of the system is diversified. In this case, the information obtained from the measurement can be analysed by an expert operator or processed by an intelligent system, obtaining in both cases information on the status of the machine under test. The second makes use of a UHF antenna built on PCB, which takes care of detecting the irradiated signal generated in the presence of discharge activity, which is then appropriately conditioned and processed by analog electronics, to then be acquired through a programmable logic, which interprets it and returns information on the status of the machine, which can also be checked by an expert user. The application of this system is linked to the type of insulation and the type of power supply adopted, which differentiate its characteristics. In both systems, the analysis of the measurement of partial discharges is suitable for the prevention of failures and the planning of suitable maintenance interventions.

Design and Realization of Electronic Measurement Systems for Partial Discharge Monitoring on Electrical Equipment

BRUZZONE, ANDREA
2021-02-25

Abstract

The monitoring of insulations that composing high voltage apparatus and electrical machines is a crucial aspect for a predictive maintenance program. The insulation system of an electrical machine is affected by partial discharges (PDs), phenomena that can lead to the breakdown in a certain time, with a consequent and significant economic loss. Partial discharges are identified as both the symptom and the cause of a deterioration of solid-type electrical insulators. Thus, it is necessary to adopt solutions for monitoring the insulation status. To do this, different techniques and devices can be adopted. During this research activity, two different systems have been developed at the circuit and layout level, which base their operation respectively on the conducted and on the irradiated measurement, in compliance with the provisions of current standards, if foreseen. The first system is based on the use of a classic signal conditioning chain in which gain value can be set through PC control, allowing the conducted measurement of partial discharges in two frequency bands, Low Frequency (LF) and High Frequency (HF). Based on these bands, the application of the system is diversified. In this case, the information obtained from the measurement can be analysed by an expert operator or processed by an intelligent system, obtaining in both cases information on the status of the machine under test. The second makes use of a UHF antenna built on PCB, which takes care of detecting the irradiated signal generated in the presence of discharge activity, which is then appropriately conditioned and processed by analog electronics, to then be acquired through a programmable logic, which interprets it and returns information on the status of the machine, which can also be checked by an expert user. The application of this system is linked to the type of insulation and the type of power supply adopted, which differentiate its characteristics. In both systems, the analysis of the measurement of partial discharges is suitable for the prevention of failures and the planning of suitable maintenance interventions.
25-feb-2021
Electronic Design, Partial discharges, Conducted system, Irradiated system
File in questo prodotto:
File Dimensione Formato  
phdunige_3831940.pdf

accesso aperto

Descrizione: Electronic Measurement Systems for Partial Discharge Monitoring on Electrical Equipment
Tipologia: Tesi di dottorato
Dimensione 8.68 MB
Formato Adobe PDF
8.68 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.